Dimensions | : | 13-1/2 in L x 4-1/2 in W x 2-1/4 in D |
Humidity Rating | : | 10 to 85% |
Interconnection Capability | : | Up to 30 Units |
Material | : | Plastic |
Operating Temperature | : | 32 to 122 deg F |
Power Source | : | 230 VAC |
Series | : | SL-2000 |
Type | : | Ionization |
Visual Alert | : | Green Pilot/Red Alarm |
Wiring Type | : | Solid/Stranded |
The SL-2000 includes many features that represent true innovations from current generation duct smoke detectors. Our traditional installer/servicer friendly approach has been closely followed and expanded throughout the SL-2000.
Apollo Duct Smoke Detector, Ionization, Series: SL-2000, 230 VAC Power Source, Up to 30 Units Interconnection, Green Pilot/Red Alarm Visual Alert, 10 to 85% Humidity, Solid/Stranded Wiring, 32 to 122 deg F Operating, Plastic, 13-1/2 in L x 4-1/2 in W x 2-1/4 in D Dimensions
- Patent pending test port valves allows for smoke testing without cover removal
- Instantaneous cover removal trouble indication
- Staggered terminal blocks for easier wiring
- 230/115/24 VAC, 24 VDC power sources
- True front loading sampling tubes
- Flashing LED on detector head indicates normal operation, more wiring space than competitive models
- Footprint allows retro fit in many applications without additional drilling
- Compatible with the WP-2000 weatherproof enclosure
- Donut gaskets on back of enclosure are pre installed
- Reset switch is also an alarm test switch competitive models require a magnet or cover removal
- Grey plastic backbox, clear plastic cover material
- 230 VAC for 26.2 mA standby current, 31.5 mA alarm current, 115 VAC for 22 mA standby current, 32 mA alarm current, 24 VAC for 14 mA standby current, 68 mA alarm current, 24 VDC for 55 mA standby current, 190 mA alarm current
- 55000-225APO detector model, air velocity 100 to 4000 ft/min
- Features high temperature and low flow
- Two sets of 10A form C alarm contacts, one set of 2 A form A alarm contacts, one set of 10 A form C trouble contacts
- 10% to 85% RH non-considering/non-freezing